Characteristic
Value
Start time for under current stage
2,
3
Typically 26 ms
Reset time for overload and alarm
stage
Typically 60 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite
time mode
1 % of the set value or ±20 ms
Operate time accuracy in inverse
time mode
10 % of the theoretical value or ±20 ms
Suppression of harmonics for under
current stage
DFT: -50 dB at f = n × fn, where n = 2,3,4,5,..
4.12.2
Current unbalance protection for capacitor banks
CUBPTOC (ANSI 60N)
4.12.2.1
Identification
Table 1063: Function identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current unbalance protection for
shunt capacitor banks
CUBPTOC
dI>C
60N
4.12.2.2
Function block
Figure 627: Function block symbol
4.12.2.3
Functionality
The current unbalance protection for shunt capacitor banks function CUBPTOC
is used to protect the double-Y-connected capacitor banks from internal faults.
CUBPTOC is suitable for the protection of internally fused, externally fused and
fuseless applications.
CUBPTOC has two stages of operation, that is, operation stage and alarm stage.
In the operating stage, CUBPTOC starts when the measured unbalance current
1
Harmonics current before fault = 0.5 × I
n
, harmonics fault current 1.5 ×
Start value, results based
on statistical distribution of 1000 measurements
2
Includes the delay of the signal output contact
3
Harmonics current before fault = 1.2 × I
n
, harmonics fault current 0.8 ×
Start value, results based
on statistical distribution of 1000 measurements
1MRS759142 F
Protection functions
REX640
Technical Manual
1119
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......