4.2.3.6
Application
INTRPTEF is an earth-fault function dedicated to operate in intermittent and
permanent earth faults occurring in distribution and sub-transmission networks.
Fault detection is done from the residual current and residual voltage signals by
monitoring the transients with predefined criteria. As the function has a dedicated
purpose for the fault types, fast detection and clearance of the faults can be
achieved.
Intermittent earth fault
Intermittent earth fault is a special type of fault that is encountered especially in
compensated networks with underground cables. A typical reason for this type of
fault is the deterioration of cable insulation either due to mechanical stress or due
to insulation material aging process where water or moisture gradually penetrates
the cable insulation. This eventually reduces the voltage withstand of the insulation,
leading to a series of cable insulation breakdowns. The fault is initiated as the
phase-to-earth voltage exceeds the reduced insulation level of the fault point and
mostly extinguishes itself as the fault current drops to zero for the first time, as
shown in
. As a result, very short transients, that is, rapid changes in the
form of spikes in residual current (Io) and in residual voltage (Uo), can be repeatedly
measured. Typically, the fault resistance in case of an intermittent earth fault is only
a few ohms.
Residual current Io and residual voltage Uo
FEEDER
FEEDER MEAS
Iov
Fault
Point
K
Re
-0.3
-0.2
-0.1
Residual
Current
(kA)
Residual
Voltage
x
10
2
(kV)
INCOMER
COMP. COIL
Ioj
Uo
K
Re
0
0.1
Ioj
(Faulty
Feeder)
Iov
(Healthy
Feeder)
Uo
Pulse width
400 - 800 s
Pulse interval
5 - 300 ms
Peak value
~0.1 ... 5 kA
Utres
Utres
I
ctot
Rf
Figure 276: Typical intermittent earth-fault characteristics
Earth-fault transients
In general, earth faults generate transients in currents and voltages. There are
several factors that affect the magnitude and frequency of these transients, such
as the fault moment on the voltage wave, fault location, fault resistance and the
parameters of the feeders and the supplying transformers. In the fault initiation,
1MRS759142 F
Protection functions
REX640
Technical Manual
487
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......