
Active
power
(P)
Rack
position
Rack
Pos
No
load
dR/dP
=
Rack
Pos
Gain
dR
dP
Figure 801: Rack position vs. Active power output of the generator
Excitation current monitoring
The excitation current,
I_EXCITATION
, produced by the AVR is compared to the
reactive power output,
Q
, of the generator. A linear relationship is assumed between
I_EXCITATION
and
Q
. The
I_EXCITATION
input is a 0-20mA signal obtained
through an
RTD
input and is in primary Amperes.
The droop characteristics can be parameterized using the settings
Ext current no
load and Ext current gain. If the performance of the generator deviates from this
relationship, the module activates the output
I_EXCT_FLT
. The module can be
disabled using the setting
Disable Ext Cur Mon.
For both the Fuel rack position monitoring and the Excitation current
monitoring modules, an internal delay of 100ms is assumed before
activation of
FUEL_RCK_FLT
and
I_EXCT_FLT
outputs. This delay is to
enable the generator mechanics to respond to the changes in fuel rack
position and excitation current.
7.5.5.3
Control logic
Once activated by either the Fuel fault detection module or by the Excitation fault
detection module, the Control logic module activates the
FLT_DETECTED
output.
This output serves as an indication for the operator or the central PMS to start
standby engines or alter the power sharing between healthy diesel generators.
If the network frequency and voltage deteriorate beyond control, the module
activates the
STOP_ENGINE
(incase of fueling faults) and
DE_EXCITE
(incase of
Condition monitoring functions
1MRS759142 F
1416
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......