The function can also be configured to handle only two-position switches (earthing
switch or disconnector).
9.2.4
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The switch type is determined depending on the connected inputs in Application
Configuration.
• If inputs
DCPOSOPEN
,
DCPOSCLOSE
,
ESPOSOPEN
and
ESPOSCLOSE
are connected,
the switch type is three-position switch.
• When only inputs
DCPOSOPEN
and
DCPOSCLOSE
are connected, the switch type is
disconnector.
• When only inputs
ESPOSOPEN
and
ESPOSCLOSE
are connected, the switch type is
earthing switch.
Any other connection leads to a configuration error.
The motor control application of the three-position switch can be selected with
parameter setting
Control mode. If "With RIO600 SCM" is selected, the motor
control is handled externally by the RIO600 SCM module; the protection relay only
supervises the switch position and interlocking but provides commands to RIO600.
If "Direct control" is selected, the motor control is handled by the protection relay’s
H-bridge and no external RIO600 SCM device is needed.
9.2.4.1
Position indication and validity check
Depending on the switch type connection, a three-position switch, disconnector or
earthing switch can be configured.
Be aware of the physical switch type and corresponding connections in
Application Configuration, both for P3SXSWI and in RIO600 SCM, if used.
A wrong connection according to the physical switch type can cause
misleading position indication.
In certain three-position switches an additional reed contact is available to indicate
safe earthing. The contact is TRUE only when the earthing switch is in closed
position. The reed contact is given a short time window to confirm closed earthing
switch position, in case of vibrations. If the earthing switch has closed but the reed
contact does not close within the time window, faulty position is reported.
Table 1474: Reed contact detection
Control mode
Reed contact detection
Direct control
The availability of the reed contact needs to be set through
the
Reed contact
setting by setting it as "Available". The reed
contact signal is connected at input
REED
.
With RIO600 SCM
Reed detection is handled externally by the module. The in-
put
ESPOSCLOSE
is not indicated TRUE by RIO600 if reed
contact closing is not detected. Therefore, unsecure earthing
is reported to input
REED_ERR
so that P3SXSWI can indicate
faulty position in this control mode.
1MRS759142 F
Control functions
REX640
Technical Manual
1521
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......