
The
IPOW_ALM
and
IPOW_LO
outputs can be blocked by activating the binary input
BLOCK
.
7.1.5.6
Remaining life of circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to
wearing. The wearing in the breaker depends on the tripping current, and the
remaining life of the breaker is estimated from the circuit breaker trip curve
provided by the manufacturer. The remaining life is decremented at least with one
when the circuit breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be
described with a module diagram. All the modules in the diagram are explained
in the next sections.
Figure 780: Functional module diagram for estimating the life of the circuit breaker
CB life estimator
CB life estimator module calculates the remaining life of the circuit breaker. The
Op number rated and Op number fault parameters set the number of operations
the breaker can perform at the rated current and at the rated fault current. If the
tripping current is lower than the rated operating current set with the
Rated Op
current setting, the remaining operation of the breaker reduces by one operation. If
the tripping current is higher than the rated fault current set with the
Rated fault
current setting, the remaining operation of the breaker reduces by Op number rated
divided by
Op number fault. The remaining life reduction of the tripping current
in between these two values is calculated based on the trip curve given by the
manufacturer.
Directional Coef
Op number fault
Op number rated
=
log
log
g
Rated fault current
Rated Op current
(Equation 319)
Remaining life reduction
Rated Op current
-Dire
=
I
fault
c
ctional Coef
(Equation 320)
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1367
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......