Power system signals are acquired, filtered and then processed by individual high-
impedance fault detection algorithm. The results of these individual algorithms are
further processed by a decision logic to provide the detection decision. The decision
logic can be modified depending on the application requirement.
Figure 671: Block diagram of PHIZ
PHIZ is based on algorithms that use earth current signatures which are considered
non-stationary, temporally volatile and of various burst duration. All harmonic and
non-harmonic components within the available data window can play a vital role
in the high-impedance fault detection. A major challenge is to develop a data
model that acknowledges that high-impedance faults could take place at any time
within the observation window of the signal and could be delayed randomly and
attenuated substantially. The model is motivated by extensive research, actual
experimental observations in the laboratory, field testing and what traditionally
represents an accurate depiction of a non-stationary signal with a time-dependent
spectrum.
Figure 672: Validation of PHIZ on gravel
Figure 673: Validation of PHIZ on
concrete
1MRS759142 F
Protection related functions
REX640
Technical Manual
1181
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......