ASGCSYN via
SRC1_ASC_DAT
...
SRC8_ASC_DAT
or from the corresponding
ASNSCSYN via signals
NS1_ASC_DAT
...
NS17_ASC_DAT
.
An example of the subnetwork group identification is shown in
. Since
NSCB 2 connects bus bar 1 and bus bar 2, then setting
NonSrc2 bus A1 Num is set
to "Bus 1" and
NonSrc2 bus A2 Num is set as "Bus 2". Based on the bus connection
status received via the input
NS2_ASC_DAT
, this module determines that Bus 1, Bus
2 and NSCB 2 are electrically connected. Similarly for SCB 2,
Src2 bus A Num is set as
"Bus 2" and the source CB closed status input is received via
SRC1_ASC_DAT
. So SCB
2 is electrically connected to Bus 2. Hence it is determined that SCB 2, Bus 2, Bus 1
and NSCB 2 are electrically connected to each other.
Two subnetworks are identified in
. The first comprises Bus 1, Bus 2,
NSCB 1, NSCB 2, SCB 2 and source 2. The second comprises Bus 3, Bus 4, NSCB 4,
SCB 3 and source 3. Each network group is assigned a subnetwork number which
is the lowest bus bar number in the subgroup. Hence the first group is assigned
subnetwork number 1 and the second group is assigned subnetwork number 3.
Source
1
Bus 3
SCB 2
NSCB 1
NSCB 2
NSCB 3
SCB 1
SCB 3
NSCB 4
Bus 4
Bus 2
Bus 1
Source
2
Source
3
Figure 886: An example of subnetwork group identification
Table 1541: ASCGAPC settings of NSCB1 for given example
Settings
Suggested values
Description
ASC CB Num1
Non source CB 1
ASC1 host circuit breaker number 1
Number of sources
3
Total number of sources present in the sys-
tem
Number of NonSrc CB 4
Number of bus coupler or grid transformer
CB in the system
Src1 bus A Num
Bus 3
Source1 CB connected bus A number
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1611
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......