and long-time thermal history, allowing more critical situations like motor start-ups
to be taken into consideration more carefully.
Setting of thermal restart level
The
Restart thermal Val can be calculated as follows:
= 100% −
−
ℎ
ℎ
∙ 100% +
(
)
(Equation 55)
For instance, if the start-up time of the motor is 4 seconds, and the calculated
operate time of the thermal protection stage for cold motor is 6 seconds, one
motor start-up will use 4/6 = 66.6% of the thermal capacity of the motor. Therefore,
the
Restart thermal Val must be set to below 100% - 66.6% = 33.3% say to 28.3%
(100% - (66.6% + margin), where margin is 5%).
Setting of thermal alarm level
Tripping due to high overload can be avoided by reducing the load of the motor
when the thermal level reaches a set alarm level.
The
Alarm thermal value can be set to a level, which will allow the use of the motor’s
full thermal capacity without causing a trip due to long time overload. Generally, the
Alarm thermal value is set to 80….90% of the trip level.
4.1.11.7
Signals
RPTTR Input signals
Table 488: RPTTR Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
U3P
SIGNAL
-
Three-phase voltages
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
START_EMERG
BOOLEAN
0=False
Signal for indicating
the need for emer-
gency start
AMB_TEMP
FLOAT32
0
The ambient temper-
ature used in the cal-
culation
Protection functions
1MRS759142 F
432
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......