9.2.4.5
Control of three-position switch using RIO600 smart control module
When using RIO600 smart control module (SCM) for controlling a three-position
switch, the setting
Control mode should be set as "With RIO600 SCM".
SCM is available with RIO600 to be able to drive a three-position switch. The
motor of the three-position switch is directly driven by the RIO600 SCM. RIO600
sends the status information to the protection relay by GOOSE communication,
and the switch position is indicated on the HMI on the protection relay. When
a three-position switch operation is requested and enabled by the protection
relay, it generates commands via
EXE_DCOPEN
,
EXE_DCCLOSE
,
EXE_ESOPEN
or
EXE_ESCLOSE
, which are transmitted to RIO600 over GOOSE communication.
Though the command handling is pre-checked by P3SXSWI, RIO600 SCM further
checks for command priority and if the requested command is allowed. The
commands are always checked on rising edge by the RIO600 SCM.
In RIO600 SCM control mode, the operation timeouts in P3SXSWI are not available
due to external motor handling by the SCM module. Status feedback from the
module is returned to the protection relay via GOOSE. The inputs for P3SXSWI
shown in
must be connected by GOOSE status signals from SCM. Input
REED
remains unconnected in this control mode.
SCMLPGGIO1.Ind10.stVal
SCMLPGGIO1.Ind11.stVal
SCMLPGGIO1.Ind12.stVal
SCMLPGGIO1.Ind13.stVal
SCMLPGGIO1.Ind14.stVal
SCMLPGGIO1.Ind15.stVal
SCMLPGGIO1.Ind16.stVal
SCMLPGGIO1.Ind17.stVal
SCMLPGGIO1.Ind1.stVal
SCMLPGGIO1.Ind2.stVal
SCMLPGGIO1.Ind3.stVal
SCMLPGGIO1.Ind4.stVal
P3SDCSWI1.OpOpn.general
P3SDCSWI1.OpCls.general
P3SECSWI1.OpOpn.general
P3SECSWI1.OpCls.general
Figure 833: Connections in P3SXSWI when using RIO600 SCM for a threeposition
switch
See the RIO600 and SCM manual when using RIO600 SCM for
threeposition switch motor control. All the signals from RIO600 must be
connected to the P3SXSWI function block as in
.
9.2.4.6
Control of three-position switch using H-bridge with static outputs
of the protection relay
When using the protection relay for direct motor control of the three-position
switch, the setting
Control mode must be set as "Direct control".
If the protection relay is equipped with static power outputs, the three-position
switch's driving motor can be controlled with an H-bridge. The function has four
outputs for motor control.
Control functions
1MRS759142 F
1526
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......