Table 603: Special conditions
Condition
Description
U3P connected to real measurements
The function can work with at least one volt-
age channel connected.
URES calculated
The function requires that all three voltage
channels from the terminal side are connec-
ted to calculate residual voltage. Setting
VT
connection
must be "Wye" in that particular
UTVTR.
UNEUT calculated
The function requires that all three voltage
channels from the neutral side are connec-
ted to calculate residual voltage. Setting
VT
connection
must be "Wye" in that particular
UTVTR.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.2.8.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are “On” and “Off”.
The operation of the third harmonic-based stator earth-fault protection function
can be described using a module diagram. All the modules in the diagram are
explained in the next sections.
START
BLOCK
UNEUT
U_3H_N
OPERATE
Level
detector
3
rd
harmonic
calculation
Timer
Differential
calculation
U3P
U_3H_A
U_3H_B
U_3H_C
GCB_CLOSED
INT_BLKD
U_3H_RES
Bias
calculation
URES
t
Figure 313: Functional module diagram
3rd harmonic calculation (terminal side)
3rd harmonic calculation calculates the magnitude and phase angle of the third
harmonic voltage at the generator terminal Ū
3H_T
. Calculation of the third harmonic
voltage depends on the availability of terminal side voltage and is specified by the
Voltage selection setting.
•
Voltage selection setting is set to "No voltage" if phase-to-earth voltages are
not available at the terminal side. Even in a situation where only phase-to-phase
voltages are available,
Voltage selection is set to "No Voltage" because phase-
to-phase voltages do not contain a third harmonic component. With
Voltage
1MRS759142 F
Protection functions
REX640
Technical Manual
543
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......