saturates. The magnetization reactance of a fully saturated CT drops to zero and the
impedance is formed only by the resistance of the winding (R
in
) and lead resistance
(R
m
).
The CT saturation causes a differential current which can flow through the
saturated CT, because of the near-zero magnetizing reactance, or through the
measuring branch. The stabilizing resistor is selected so that the current in the
measuring branch is below the protection relay's operating current during out-of-
zone faults. As a result, the operation is stable during the saturation and can still be
sensitive at the undistorted parts of the current waveform.
Figure 460: Three-phase differential protection for motors based on highimpedance
principle
In case of an internal fault, the fault current cannot circulate through the CTs. It
flows through the measuring branch, and the protection operates. A partial CT
saturation can occur in case of an internal fault, but the undistorted part of the
current waveform causes the protection to operate.
Figure 461: Secondary waveform of a saturated CT
Protection functions
1MRS759142 F
808
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......