Figure 802: Example application configuration for real and reactive power
connection
Once a generator is identified faulty an indication is sent to PMS for starting the
backup generators, or to alter the power sharing between healthy generators, which
would allow the faulty generator to be offloaded and tripped. But in case the
system deteriorates, the function issues commands to shut down the engine or
de-excite the generator. It then issues the command to open the GCB. In case the
GCB tripping is unsuccessful, the function opens the neighboring tie breakers.
The network topology identification enables the function to locate a particular fault
in the network and trip the neighboring tie breakers of healthy generators in case a
network generator is faulty and is still not tripped.
The application configuration needs to ensure that in case any protection
functions like, over speed protection or over voltage protection or if
generator operates outside stability limit then a signal needs to be sent
to shut down the diesel engine and open the GCB.
This needs to be configured outside the DGMGAPC function block.
The function monitors the fuel rack position and excitation current of the generator
and rises an alarm in case they are deviating from the set operation mode.
7.5.7
Signals
Condition monitoring functions
1MRS759142 F
1420
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......