Parameter
Values (Range)
Unit
Step
Default
Description
Current dead Lin
Val
0.01...1.00
xIn
0.01
0.20
Dead line value,
current. Used also
in auto activation
logic
Voltage dead Lin
Val
0.01...0.58
xUn
0.01
0.40
Dead line value,
voltage. Used also
in auto activation
logic
Cur voltage Det
time
0...60000
ms
10
20
Time delay for volt-
age and current
based detection
Operate time delay 0...120000
ms
10
20
Delay for the de-
layed start input
SOTF reset time
0...60000
ms
10
1000
SOTF detection pe-
riod after initializa-
tion
Dead line time
0...60000
ms
10
200
Delay time for acti-
vation of dead line
detection
5.8.9
CVPSOF Monitored data
Table 1173: CVPSOF Monitored data
Name
Type
Values (Range)
Unit
Description
CVPSOF
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
1MRS759142 F
Protection related functions
REX640
Technical Manual
1229
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......