Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
Internal Fault
PO-relay(s), Slot
F
-25
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot F.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot F.
Internal Fault
PO-relay(s), Slot
G
-26
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot G.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot G.
Internal Fault
PO-relay(s), Slot
A1
-27
Runtime error:
Faulty Power Out-
put relay(s) in card
located in slot A1.
Yes
Yes (3)
No
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A1.
Internal Fault
Conf. error, Slot
C
-30
Start up error: Card
in slot C is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
C is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot C.
Internal Fault
Conf. error, Slot
E
-31
Start up error: Card
in slot E is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
E is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot E.
Internal Fault
Conf. error, Slot
A2
-32
Start up error: Card
in slot A2 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the communica-
tion card in slot A2 is prop-
er type and properly instal-
led. Then restart the relay.
If does not then recover by
restarting, it is hardware
module failure most likely
in question. Exchange the
communication module in
slot A2.
Internal Fault
Conf. error, Slot
B
-33
Start up error: Card
in slot B is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
B is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot B.
Internal Fault
Conf. error, Slot
D
-34
Start up error: Card
in slot D is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
No
No
Yes
Check that the card in slot
D is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
Table continues on the next page
1MRS759142 F
Basic functions
REX640
Technical Manual
105
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......