Parameter
Values (Range)
Unit
Step
Default
Description
Coarse Volt Diff Un 0.00...0.40
xUn
0.01
0.03
Maximum voltage
difference limit
allowed during
matching
Angle Diff positive
5...90
deg
1
5
Maximum angle
difference limit
Angle Diff negative 5...90
deg
1
5
Maximum angle
difference limit
Volt rate of change 0.001...0.050
xUn/s
0.001
0.003
dU/dt adapted to
AVR for voltage
matching pulses
Freq rate of change 0.001...0.050
xFn/s
0.001
0.002
dF/dt adapted to
governor for fre-
quency matching
pulses
Table 1522: ASGCSYN Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Phase shift
-180...180
deg
1
0
Correction of phase
difference between
measured voltages
Closing time of CB
40...250
ms
1
60
Closing time of the
breaker
Multiple command 0=Off
1=On
0=Off
Multiple command
generation
Synchronization Dir 1=Always over syn-
chronous
2=Both direction
2=Both direction
Synchronization di-
rection
Voltage offset
-0.100...0.100
xUn
0.001
0.000
Voltage offset
Frequency offset
-0.010...0.010
xFn
0.001
0.000
Frequency offset
Table 1523: ASGCSYN Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Synchrocheck
mode
1=Off
3=Asynchronous
4=Command
3=Asynchronous
Synchrocheck oper-
ation mode
Dead voltage value 0.10...0.80
xUn
0.10
0.20
Voltage low lim-
it for energizing
check
Live voltage value
0.20...1.00
xUn
0.10
0.50
Voltage high lim-
it for energizing
check
Maximum voltage
0.50...1.30
xUn
0.01
1.05
Maximum voltage
above which no
paralleling takes
place
Minimum voltage
0.50...0.95
xUn
0.01
0.80
Minimum voltage
below which no
paralleling takes
place
Voltage match
mode
1=Off
2=Variable Pulse
3=Variable Interval
2=Variable Pulse
Voltage matcher
mode
Frequency match
mode
1=Off
2=Variable Pulse
Frequency matcher
mode
Table continues on the next page
1MRS759142 F
Control functions
REX640
Technical Manual
1583
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......