Table 1219: Analog inputs
Input
Description
I3P
1
Three-phase currents, necessary when Pol quantity is "Neg.
seq. volt."
IRES
2
Residual current (measured or calculated), necessary when
Pol quantity is "Zero seq. volt."
U3P
1
Three-phase voltages, necessary when Pol quantity is "Neg.
seq. volt."
URES
2
Residual voltage (measured or calculated), necessary when
Pol quantity is "Zero seq. volt."
See the preprocessing function blocks in this document for the possible
signal sources.The
GRPOFF
signal is available in the function block called
Protection.
There are a few special conditions which must be noted with the configuration.
Table 1220: Special conditions
Condition
Description
U3P connected to real meas-
urements
The function can work with any two phase voltage channels
connected but it is recommended to connect all three volt-
age channels.
URES calculated
The function requires that all three voltage channels are con-
nected to calculate residual voltage. Setting
VT connection
must be "Wye" in that particular UTVTR.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
5.15.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "on" and "off".
The operation of DNZSRDIR can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
1
Can be connected to
GRPOFF
if
Pol quantity is set to "Zero seq. volt.".
2
Can be connected to
GRPOFF
if
Pol quantity is set to "Neg. seq. volt.".
1MRS759142 F
Protection related functions
REX640
Technical Manual
1287
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......