
Parameter
Values (Range)
Unit
Step
Default
Description
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Operate delay time 40...300000
ms
10
40
Operate delay time
Characteristic an-
gle
-179...180
deg
1
60
Characteristic an-
gle
Max forward angle
0...90
deg
1
80
Maximum phase
angle in forward di-
rection
Max reverse angle
0...90
deg
1
80
Maximum phase
angle in reverse di-
rection
Min forward angle
0...90
deg
1
80
Minimum phase an-
gle in forward di-
rection
Min reverse angle
0...90
deg
1
80
Minimum phase an-
gle in reverse direc-
tion
Table 407: DPHHPDOC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate
Selection of reset
curve type
Voltage Mem time
0...3000
ms
1
40
Voltage memory
time
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
5=Cross pol
Reference quantity
used to determine
fault direction
Table 408: DPHHPDOC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Curve parameter A 0.0086...120.0000
0.0001
28.2000
Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120
0.0001
0.1217
Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00
0.01
2.00
Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00
0.01
29.10
Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0
0.1
1.0
Parameter E for
customer program-
mable curve
Num of start pha-
ses
1=1 out of 3
2=2 out of 3
1=1 out of 3
Number of phases
required for oper-
ate activation
1MRS759142 F
Protection functions
REX640
Technical Manual
365
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......