Frequency slip(s)
=
−
(
)
f
f
f
Gen
Bus
Bus
(Equation 358)
The measured bus voltage (U
Bus
), bus frequency (f
Bus
), generator voltage (U
Gen
),
generator frequency (f
Gen
) and phase angle difference values between the two
sides of the circuit breaker are available as monitored data values U_BUS_MEAS,
FR_BUS_MEAS, U_GEN_MEAS, FR_GEN_MEAS, U_DIFF_MEAS, FR_DIFF_MEAS and
PH_DIFF_MEAS. The calculated frequency slip acceleration (ds/dt) is available as
monitored data value FR_SLIP_ACCL. Also, the indications of the conditions that
are not fulfilled and thus preventing the breaker closing permission are available
as monitored data values U_DIFF_SYNC, PH_DIF_SYNC and FR_DIFF_SYNC. These
monitored data values are updated only when the setting
Synchrocheck mode is set
to "Asynchronous" and the measured ENERG_STATE is "Both Live".
The measured voltage, frequency are updated in the monitored data irrespective of
any condition.
Close CB condition
When
Synchrocheck mode is set to "Asynchronous", the close CB condition is
generated as explained below.
From the frequency slip s, the acceleration ds/dt, the bus frequency FR_BUS_MEAS
(f
Bus
) and the set
Closing time of CB, the function calculates the necessary lead
angle (α
Lead
) by which the close CB command is shifted forward in time so that the
main contacts close on phase coincidence.
α
Lead
Bus
f
s
TCB ds
dt
TCB
=
⋅
⋅
+
⋅
⋅
360
2
1000
1000
(Equation 359)
f
Bus
Bus side frequency
s
Frequency slip
ds/dt
Frequency slip acceleration
TCB
Setting
Closing time of CB
ASGCSYN can be set to the bypass mode by setting the parameters
Synchrocheck mode and Live dead mode to "Off" or, alternatively, by
activating the
BYPASS
input. In the bypass mode, the close CB conditions
are always fulfilled. Otherwise, the operation is similar to the normal
mode.
If the parameter
Synchronization Dir is “Both directions”, function issues
CLOSE_CB
output direct-ly when the measured frequency difference is
zero and the measured phase difference is less than 5 degrees for
duration set by
Minimum Syn time.
If the parameter
Synchronization Dir is “Always over-synchronous”,
closing signal is blocked when the measured frequency difference is
between 0 and 1/3*
Freq Diff Ov Synch.
Control functions
1MRS759142 F
1564
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......