9.4.2
Function block
Figure 840: Function block
Figure 841: Function block
9.4.3
Functionality
The functions DCSXSWI and ESSXSWI indicate remotely and locally the open, close
and undefined states of the disconnector and earthing switch. The functionality
of both is identical, but each one is allocated for a specific purpose visible in
the function names. For example, the status indication of disconnectors or circuit
breaker truck can be monitored with the DCSXSWI function.
The functions are designed according to the IEC 61850-7-4 standard with the logical
node XSWI.
9.4.4
Operation principle
Status indication and validity check
The object state is defined by the two digital inputs
POSOPEN
and
POSCLOSE
, which
are also available as outputs
OPENPOS
and
CLOSEPOS
together with the
OKPOS
according to
. The debounces and short disturbances in an input are
eliminated by filtering. The binary input filtering time can be adjusted separately
for each digital input used by the function block. The validity of digital inputs that
indicate the object state is used as additional information in indications and event
logging.
Table 1491: Status indication
Input
Status
Output
POSOPEN
POSCLOSE
POSITION
(Monitored
data)
OKPOS
OPENPOS
CLOSEPOS
1=True
0=False
1=Open
1=True
1=True
0=False
0=False
1=True
2=Closed
1=True
0=False
1=True
1=True
1=True
3=Faulty/Bad
(11)
0=False
0=False
0=False
0=False
0=False
0=Intermedi-
ate (00)
0=False
0=False
0=False
Control functions
1MRS759142 F
1540
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......