1. Setting
Maximum earthing Ris is used to scale the touch voltage and earth
potential rise requirements defined in standard EN 50522 into corresponding
earth-fault current requirements.
2. Setting
UTp multiplier enables operation based on permissible earth potential
rise U
E
, by scaling of the permissible time-touch voltage characteristics given in
standard EN 50522 with Setting
UTp multiplier, see table below.
Table 627: Permissible touch voltages U
Tp
and earth potential rise U
E
values
given in standard EN50522 converted into equivalent permissible earth-fault
current I
Fp
values as a function of the fault duration t
f
. Conversion is made
with parameter R
Emax
, which is the setting
Maximum earthing Ris in primary
ohms i.e. the maximum earthing resistance encountered in protected feeder.
Fault duration t
f
[sec.]
Permissible touch
voltage, U
Tp
converted into
corresponding
permissible fault
current, I
Fp
, U
Tp
multiplier = 1.0 [A]
Permissible earth
potential rise,
U
E
converted
into corresponding
permissible fault
current, I
Fp
, U
Tp
multiplier = 2.0 [A]
Permissible earth
potential rise,
U
E
converted
into corresponding
permissible fault
current, I
Fp
, U
Tp
multiplier = 4.0 [A]
0.05
716 V/R
Emax
1432 V/R
Emax
2864 V/R
Emax
0.10
654 V/R
Emax
1308 V/R
Emax
2616 V/R
Emax
0.20
537 V/R
Emax
1074 V/R
Emax
2148 V/R
Emax
0.50
220 V/R
Emax
440 V/R
Emax
880 V/R
Emax
1.00
117 V/R
Emax
234 V/R
Emax
468 V/R
Emax
2.00
96 V/R
Emax
192 V/R
Emax
384 V/R
Emax
5.00
86 V/R
Emax
172 V R
Emax
344 V/R
Emax
10.00
85 V/R
Emax
170 V/R
Emax
340 V/R
Emax
3. Minimum effective earth-fault current magnitude (considering the effect of
setting
Reduction factor), which must be exceeded for the function to start,
is defined with setting
EF current Str Val. It is important to set this value
according to required protection sensitivity.
4. With
IDMT stage Min Op Tm setting user can define minimum allowed operate
time for IFPTOC i.e. this is the minimum allowed operate time of IFPTOC.
5. With
IDMT stage Max Op Tm setting user can define maximum allowed operate
time for IFPTOC i.e. this is the maximum allowed operate time of IFPTOC
although IDMT timer would define slower operate time.
Parameter defining maximum earthing resistance, setting
Maximum
earthing Ris must be always set in case Operation principle = “EF current
based” and
Operating curve type = “Inverse time EN50522” is selected.
Setting
Maximum earthing Ris is needed to scale the touch voltage and
earth potential rise requirements defined in standard EN 50522 into
corresponding earth-fault current requirements.
Setting
Reduction factor considers the fact that only part of the earth-
fault current (I
F
) will flow back through “remote” earth and introduces
earth potential rise and touch voltages.
Minimum practical value for setting
EF current Str Val is 0.5% from CT
primary current. For example, in case CT primary current is 200A, then
minimum practical value for setting
EF current Str Val is 0.5%*200 A =
1 A. For CT with 400 A primary current, then minimum practical value
Protection functions
1MRS759142 F
602
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......