until the 10 minute time-out has passed or until the emergency start is released,
whichever takes longer.
The last change of the emergency start output signal is recorded.
5.6.7
Signals
5.6.7.1
ESMGAPC Input signals
Table 1140: ESMGAPC Input signals
Name
Type
Default
Description
I3P
SIGNAL
-
Three-phase currents
BLOCK
BOOLEAN
0=False
Block signal for acti-
vating the blocking
mode
ST_EMERG_RQ
BOOLEAN
0=False
Emergency start in-
put
5.6.7.2
ESMGAPC Output signals
Table 1141: ESMGAPC Output signals
Name
Type
Description
ST_EMERG_ENA
BOOLEAN
Emergency start
5.6.8
ESMGAPC Settings
Table 1142: ESMGAPC Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Motor standstill A
0.01...0.20
xIn
0.01
0.12
Current limit to
check for motor
standstill condition
Table 1143: ESMGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
5.6.9
ESMGAPC Monitored data
Protection related functions
1MRS759142 F
1192
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......