and has thus value of 1. 0pu (xU
n_PE
, U
n_PE
= Nominal phase-to-earth voltage). In the
middle column is shown residual voltage, phase currents and fault current estimate
during a higher ohmic earth fault (R
F
= 3000 ohm). During a higher ohmic earth
fault U
o
reduces and thus also the magnitude of fault current is reduced. But the
magnitude of fault current is reduced proportionally to residual voltage. In the
right-hand column the effect of fault resistance is compensated by scaling the fault
current estimate by dividing it with the per unit value of residual voltage. With fault
resistance compensation, the operation speed of IFPTOC can be accelerated during
high(er) ohmic earth faults.
Figure 339: Illustration of fault resistance compensation functionality in IFPTOC. Left-hand column:
galvanic earth fault (R
F
= 0 ohm). Middle column: a higher ohmic earth fault (R
F
= 3000 ohm) with
setting Ena R
F
Compensation = “Disable”. Right-hand column: a higher ohmic earth fault (R
F
= 3000
ohm) with setting Ena R
F
Compensation = “Enable”.
Note that it is the “effective” earth-fault current estimate which determines
operation of IFPTOC. “Effective” earth-fault current includes the effect of user
setting
Reduction factor:
Effective earth-fault current estimate,
:
(Equation 115)
Setting
Reduction factor is a user defined reduction factor, which can be used to
scale down the estimated earth-fault current magnitude. Setting
Reduction factor
allows e.g. consideration that not all the earth-fault current (I
F
) will flow back
through “remote” earth. See illustration in Figure 7. A portion of the earth-fault
current (I
SCR
) may have alternative return paths, e.g. through cable sheaths/screens.
Only current which flows through earth (I
E
) will introduce rise of earth potential
(earth potential rise, EPR, also called as ground potential rise GPR), which must
1MRS759142 F
Protection functions
REX640
Technical Manual
593
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......