B1. Thus, when the breaker at Relay B1 opens, the direction of the fault current at the
healthy feeder (Feeder 2) is reversed.
Figure 720: The circuit breaker at Relay B1 opens and creates a current reversal condition
Relay A2 is still sending the CS signal because of the reset time delay of the forward
zone of Relay A2 when the overreaching zone of Relay B2 starts to recognize the
fault in the forward direction. Relay B2 can malfunction and trip the breaker of the
healthy feeder.
This problem can be solved by using the reverse-looking zone (Z3) to recognize the
fault in reverse direction and temporarily block the operation of DSOCPSCH due to
the current reversal condition. This is used in CRWPSCH.
Weak-end infeed logic
Avoid using the WEI function at both feeder ends. It can only be enabled
at the weak end.
The weak-end infeed logic should be used only in permissive schemes.
Setting guidelines for current reversal logic
Setting
Reversal reset time: Set the Reversal reset time setting to the maximum
reset time of the communication channel. A minimum setting of 40 ms is
recommended. A long
Reversal reset time setting increases the security against
unwanted tripping, but delays the fault clearing if the fault develops in one feeder
and involves the other. However, the probability of this type of fault is small.
Setting
Reversal time: Set the start delay Reversal time setting to less than 80
percent of the breaker operate time, but to a minimum of 20 ms.
Protection related functions
1MRS759142 F
1270
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......