groups or the
RCA_CTL
input. Alternatively, the operating sector of the directional
earth-fault protection function can be extended to cover the operating sectors of
both neutral earthing principles. Such characteristic is valid for both unearthed and
compensated network and does not require any modification in case the neutral
earthing changes temporarily from the unearthed to compensated network or vice
versa.
The extended phase angle characteristic is created by entering a value of over 90
degrees for the
Min forward angle setting; a typical value is 170 degrees ( Min
reverse angle in case Directional mode is set to "Reverse"). The Max forward angle
setting should be set to cover the possible measurement inaccuracies of current
and voltage transformers; a typical value is 80 degrees (
Max reverse angle in case
Directional mode is set to "Reverse").
Figure 261: Extended operation area in directional earth-fault protection
4.2.2.7
Measurement modes
The function operates on three alternative measurement modes: "RMS", "DFT" and
"Peak-to-Peak". The measurement mode is selected with the
Measurement mode
setting.
Table 534: Measurement modes supported by DEFxPDEF stages
Measurement mode
DEFLPDEF
DEFHPDEF
RMS
x
x
DFT
x
x
Peak-to-Peak
x
x
1MRS759142 F
Protection functions
REX640
Technical Manual
463
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......