Parameter
Values (Range)
Unit
Step
Default
Description
Characteristic an-
gle
-179...180
deg
1
-90
Characteristic an-
gle
Time multiplier
0.025...2.000
0.005
1.000
Time multiplier for
Wattmetric IDMT
curves
Operating curve
type
5=ANSI Def. Time
15=IEC Def. Time
20=Wattmetric
IDMT
15=IEC Def. Time
Selection of time
delay curve type
Operate delay time 60...300000
ms
10
60
Operate delay time
for definite time
Table 598: WPWDE Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 599: WPWDE Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used cur-
rent measurement
mode
Correction angle
0.0...10.0
deg
0.1
2.0
Angle correction
Min operate current 0.010...1.000
xIn
0.001
0.010
Minimum operating
current
Min operate volt-
age
0.01...1.00
xUn
0.01
0.01
Minimum operating
voltage
Reset delay time
0...60000
ms
1
20
Reset delay time
Pol reversal
0=False
1=True
0=False
Rotate polarizing
quantity
4.2.7.11
WPWDE Monitored data
Table 600: WPWDE Monitored data
Name
Type
Values (Range)
Unit
Description
FAULT_DIR
Enum
0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time / op-
erate time
DIRECTION
Enum
0=unknown
1=forward
2=backward
3=both
Direction information
ANGLE
FLOAT32
-180.00...180.00
deg
Angle between polar-
izing and operating
quantity
Table continues on the next page
Protection functions
1MRS759142 F
540
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......