Pol reversal parameter to "True" or by switching the polarity of the residual
voltage measurement wires. Although the Iosin(φ) operation can be used in solidly
earthed networks, the phase angle is recommended.
Connection of measuring transformers in directional earth fault applications
The residual current Io can be measured with a core balance current transformer or
the residual connection of the phase current signals. If the neutral of the network is
either isolated or earthed with high impedance, a core balance current transformer
is recommended to be used in earth-fault protection. To ensure sufficient accuracy
of residual current measurements and consequently the selectivity of the scheme,
the core balance current transformers should have a transformation ratio of at least
70:1. Lower transformation ratios such as 50:1 or 50:5 are not recommended.
Attention should be paid to make sure the measuring transformers are connected
correctly so that DEFxPDEF is able to detect the fault current direction without
failure. As directional earth fault uses residual current and residual voltage (-Uo),
the poles of the measuring transformers must match each other and also the fault
current direction. Also the earthing of the cable sheath must be taken into notice
when using core balance current transformers. The following figure describes how
measuring transformers can be connected to the protection relay.
Figure 271: Connection of measuring transformers
4.2.2.11
Signals
Protection functions
1MRS759142 F
474
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......