Reliable directional calculation requires that both negative-sequence current and
negative-sequence voltage quantities exceed certain minimum amplitude levels. The
minimum amplitude level for the negative-sequence current is set with the
Min
operate current setting. The minimum amplitude level for the polarizing quantity,
that is, the negative-sequence voltage, is set with the
Min operate voltage setting.
If the amplitude level of the operating quantity or polarizing quantity is below the
set level, the direction information of the corresponding phase is set to “unknown”.
If the negative-sequence voltage before the fault situation is below
Min operate
voltage, the voltage direction cannot be determined.
The value for the
Min operate voltage setting should be carefully selected
since the accuracy in low signal levels is strongly affected by the
measuring device accuracy.
Timer
Once activated, Timer activates the
START
output. The time characteristic is
according to DT. When the operation timer has reached the value set by
Operate
delay time, the
OPERATE
output is activated if the operating signal persists.
In a drop-off situation, that is, if a fault suddenly disappears before the operate
delay is exceeded, the timer reset state is activated. If the reset timer reaches
the value set by
Reset delay time, the operate timer resets and the
START
output
is deactivated. The timer calculates the start duration value START_DUR, which
indicates the percentage ratio of the start situation and the set operation time.
The value is available in the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the
BLOCK
signal activation
is preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the “Freeze timers”
mode, the operation timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the “Block all” mode, the whole
function is blocked and the timers are reset. In the “Block OPERATE output” mode,
the function operates normally but the
OPERATE
output is not activated.
4.4.2.6
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area
is limited with the
Min forward angle and Max forward angle settings. The reverse
operation area is limited with the
Min reverse angle and Max reverse angle settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle setting gives the
counterclockwise sector and the
Min forward angle setting gives the corresponding
clockwise sector, measured from the
Characteristic angle setting.
In the backward operation area, the
Max reverse angle setting gives the
counterclockwise sector and the
Min reverse angle setting gives the corresponding
Protection functions
1MRS759142 F
828
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......