Characteristic
Value
Transient overreach SIR = 0.1...50
<8.5%
Reset time
Typically 45 ms
Reset ratio
Typically 0.96/1.04
Operate time accuracy
±1.0% of the set value or ±20 ms
4.7.1.12
Technical revision history
Table 934: DSTPDIS Technical revision history
Product connectivity
level
Technical revision
Change
PCL4
B
New outputs added: DIRECTION_Z1...Z5. Set-
ting
Factor K0 zone 1...5
range extended to
0.00...5.00. Setting
Factor K0 angle Zn1...5
range extended to -180...180. Setting
Min
phase angle zone
range extended to 90....150.
Setting
Max phase angle zone
range exten-
ded to 0...60
4.7.2
Out of step OOSRPSB (ANSI 78PS)
4.7.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Out-of-step protection with double
blinders
OOSRPSB
OOS
78PS
4.7.2.2
Function block
Figure 558: Function block
4.7.2.3
Functionality
The Out-of-step protection with double blinders function OOSRPSB detects out of
step conditions by monitoring impedance.
2
SIR = Source impedance ratio
1MRS759142 F
Protection functions
REX640
Technical Manual
1005
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......