The counters are reset through communication with the
CntRs parameter. The same
functionality can also be found in the clear menu (DARREC1 counters).
9.9.6
Application
Modern electric power systems can deliver energy to users very reliably. However,
different kind of faults can occur. Protection relays play an important role in
detecting failures or abnormalities in the system. They detect faults and give
commands for corresponding circuit breakers to isolate the defective element
before excessive damage or a possible power system collapse occurs. A fast
isolation also limits the disturbances caused for the healthy parts of the power
system.
The faults can be transient, semi-transient or permanent. Permanent fault, for
example in power cables, means that there is a physical damage in the fault location
that must first be located and repaired before the network voltage can be restored.
In overhead lines, the insulating material between phase conductors is air. The
majority of the faults are flash-over arcing faults caused by lightning, for example.
Only a short interruption is needed for extinguishing the arc. These faults are
transient by nature.
A semi-transient fault can be caused for example by a bird or a tree branch falling
on the overhead line. The fault disappears on its own if the fault current burns the
branch or the wind blows it away.
Transient and semi-transient faults can be cleared by momentarily de-energizing
the power line. Using the auto-reclose function minimizes interruptions in the
power system service and brings the power back on-line quickly and effortlessly.
The basic idea of the auto-reclose function is simple. In overhead lines, where the
possibility of self-clearing faults is high, the auto-reclose function tries to restore
the power by reclosing the breaker. This is a method to get the power system back
into normal operation by removing the transient or semi-transient faults. Several
trials, that is, autoreclose shots are allowed. If none of the trials is successful and
the fault persists, definite final tripping follows.
The auto-reclose function can be used with every circuit breaker that has the
ability for a reclosing sequence. In DARREC auto-reclose function the implementing
method of auto-reclose sequences is patented by ABB.
Table 1559: Important definitions related to auto-reclosing
Autoreclose
shot
An operation where after a preset time the breaker is closed from the
breaker tripping caused by protection.
Autoreclose se-
quence
A predefined method to do reclose attempts (shots) to restore the power
system.
SOTF
If the protection detects a fault immediately after an open circuit breaker
has been closed, it indicates that the fault was already there. It can be,
for example, a forgotten earthing after maintenance work. Such closing of
the circuit breaker is known as switch on to fault. Autoreclosing in such
conditions is prohibited.
Final trip
Occurs in case of a permanent fault, when the circuit breaker is opened
for the last time after all programmed autoreclose operations. Since no
auto-reclosing follows, the circuit breaker remains open. This is called
final trip or definite trip.
Control functions
1MRS759142 F
1678
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......