
Motor logic and parameters
To prevent damage to the motor, the motor is protected by several settable
timeouts. With setting parameter
Motor start timeout, the maximum start time
for the motor to recognize a position indication change is defined. If a position
indication change is not recognized during this time, the motor is stopped. If
Motor
start timeout is set to zero, the motor start timeout is disabled.
With timeout
Operation timeout DC, the maximum time for the disconnector to go
from one state to another is defined.
With timeout
Operation timeout ES, the maximum time for the earthing switch to
go from one state to another is defined. If a state change is not fulfilled within this
time, the motor is stopped.
If an unexpected position is detected based on the requested command, in other
words the motor is running in the wrong direction, or if faulty position of the
switch is detected, the motor is immediately stopped. Additionally, an activated
block input that corresponds to the active command stops the running motor
immediately.
If any of the cases above occur, the specific event is displayed on the HMI or
reported via communication.
When the motor operates and reaches the final destination, the motor brakes if
the
Motor braking setting is selected as "True". The braking time of the motor
is selectable with the
Motor brake time parameter. After the motor has braked
and stopped, the motor is in a free state, meaning that the switch is mechanically
operable by hand-crank. A successful operation is also displayed on the HMI or
reported via communication.
After each operation the motor is paused for one second before any new control
command can pass through.
9.2.4.7
Control methods
The command execution mode can be set with the
Control model setting. The
alternatives for command execution are direct control and secured object control,
which can be used to secure controlling.
The secured object control SBO is an important feature of the communication
protocols that support horizontal communication, because the command
reservation and interlocking signals can be transferred with a bus. All secured
control operations require two-step commands: a selection step and an execution
step. The secured object control is responsible for several tasks.
• Command authority: ensures that the command source is authorized to operate
the object.
• Mutual exclusion: ensures that only one command source at a time can control
the object.
• Interlocking: allows only safe commands.
• Execution: supervises the command execution.
• Command canceling: cancels the controlling of a selected object.
In direct operation, a single message is used to initiate the control action of a
physical device. The direct operation method uses less communication network
capacity and bandwidth than the SBO method, because the procedure needs fewer
messages for accurate operation.
Control functions
1MRS759142 F
1528
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......