Low
operate
value
Slope
section
2
End
section
2
Curve
1
2
3
50 %Ir
20 %Ir
50 %
100 %Ir
30 %
150 %Ir
5 %Ir
10 %
500 %Ir
Curve 1
Curve 2 ( Default settings )
Curve 3
I
d
[%I
r
]
I
d
[%I
r
]
Figure 412: Setting range for biased low stage
If the biasing current is small compared to the differential current or if the phase
angle between the currents of two windings with the highest phase current is
close to zero (normally, the phase difference is 180 degrees) or the phase angle
between the compared phase currents (in case of two-winding transformer) is close
to zero, a fault has most certainly occurred in the area protected by the differential
protection relay. The internal blocking signals of the biased stage are inhibited.
The operation of the differential protection is based on the fundamental frequency
components. The operation is accurate and stable: the DC component and
harmonics of the current do not cause unwanted operations.
Instantaneous high stage
Instantaneous high stage can be enabled or disabled with the
Enable high set
setting. The corresponding parameter values are "True" and "False".
The operation of Instantaneous high stage is not biased. The instantaneous
stage operates and the
OPR_HS
output is activated when the amplitude of the
fundamental frequency component of the differential current exceeds the set
operation value
High operate value or when the instantaneous value of the
differential current exceeds 2.5 ·
High operate value. The value 2.5 (=1.8 · √2) is due to
the maximum asymmetric short circuit current.
If the biasing current is small compared to the differential current, or if the phase
angle between the currents of the two windings with the highest phase current is
close to zero (normally, the phase difference is 180 degrees) or the phase angle
between the compared phase currents (in case of a two-winding transformer)
is close to zero, a fault has occurred in the area protected by the differential
protection. The operating value set for the instantaneous stage is automatically
halved and the internal blocking signals of the biased stage are inhibited.
Protection functions
1MRS759142 F
728
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......