Under frequency initiation
Function monitors the active supply feeder frequency. If under frequency initiation
is enabled, then transfer is initiated if the supply feeder frequency falls below
the set value. The threshold can be set with a setting
Start Val frequency. Under
frequency initiation is enabled if
Operation mode setting is “Freq<” or “Freq< or U<”.
Under frequency transfer initiation can be delayed with a setting
Under frequency
time.
Output
INIT_UF
is activated if transfer is initiated by internal under frequency
initiation. Output
INIT_UF
can be activated only if function is ready for transfer, i.e.
READY
output is active.
Under voltage initiation
Function monitors the active supply feeder voltage. If under voltage initiation is
enabled, then transfer is initiated if any the connected supply feeder voltages fall
below the set value. The threshold can be set with a setting
Start Val voltage. Under
voltage initiation is enabled if
Operation mode setting is “U<“ or “Freq< or U<”.
Under voltage-based transfer initiation can be delayed with a setting
Under voltage
time.
Output
INIT_UV
is activated if transfer is initiated by internal under voltage
initiation. Output
INIT_UV
can be activated only if function is ready for transfer,
i.e.
READY
output is active.
External transfer initiation
The bus transfer action can be initiated externally by different inputs:
• INIT_TR_1_2 – Initiates any enabled transfer from feeder 1 to feeder 2
• INIT_TR_2_1 – Initiates any enabled transfer from feeder 2 to feeder 1
• INIT_MANUAL – Initiates manual transfer, transfer direction depends on which
direction is enabled in transfer direction block
Bus transfer initiation can be disabled with different inputs:
• DISA_INIT – Disables all transfers
• DISA_1_2 – Disables all transfers from feeder 1 to feeder 2
• DISA_2_1 – Disables all transfers from feeder 2 to feeder 1
If transfer initiation is signaled to direction that is allowed, transfer initiation is
signaled to Bus transfer module (transfer initiation).
Output
INIT_EXT
is activated if transfer is initiated by external initiation. Output
INIT_EXT
can be activated only if function is ready for transfer, i.e. READY signal
(from Evaluation module) is active.
When function is ready for transfer, this is shown with output
READY
. If transfer
initiation is not possible, then
NOT_READY
output is activated.
Output
INIT_MAN
is activated if transfer is initiated manually. Output
INIT_MAN
is
activated only if function is ready for transfer, i.e. READY signal (from Evaluation
module) is active. Manual initiation is controlled by
Manual transfer setting as
explained in
1MRS759142 F
Control functions
REX640
Technical Manual
1769
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......