Id/Ir
Ib/Ir
Slope
section 2
Low operate value
OPERATE
AREA (LS)
NON-OPERATE
AREA (LS & HS)
End section 1
High operate value
OPERATE
AREA (HS)
Slope
section 3
End section 2
NON-OPERATE
AREA (LS)
Figure 413: Operating characteristics of the protection. LS stands for the biased low
stage and HS for the instantaneous high stage
The
OPERATE
output is always activated with the
OPR_HS
output. The internal
blocking signals of the differential function do not prevent the trip signal of the
instantaneous differential current stage from being activated. When required, the
operating outputs of Instantaneous high stage can be blocked by the external
control signals
BLK_OPR_HS
or
BLOCK
.
OPERATE
I_D
(from Differential calculation)
High operate value
OPR_HS
BLOCK
BLK_OPR_HS
Fault in protected area
(from Differential calculation)
Figure 414: Operation logic of Instantaneous high stage
External blocking functionality
TR3PTDF has three inputs for blocking.
1MRS759142 F
Protection functions
REX640
Technical Manual
729
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......