Start of element
START_GFC STARTS_GF
C
RELEASE_P
E
RELEASE_P
P
I
B
> & I
C
>
TRUE
BC Fault
No fault
BC Fault
I
C
> & I
A
>
TRUE
CA Fault
No fault
CA Fault
I
A
> & I
B
> &
EARTH_FLT
TRUE
AB Fault
AB Fault
AB Fault
I
B
> & I
C
> &
EARTH_FLT
TRUE
BC Fault
BC Fault
BC Fault
I
C
> & I
A
> &
EARTH_FLT
TRUE
CA Fault
CA Fault
CA Fault
I
A
> & I
B
> & I
C
4
TRUE
ABC Fault
No fault
ABC Fault
I
A
> & I
B
> & I
C
> &
EARTH_FLT
5
TRUE
ABC Fault
ABC Fault
ABC Fault
In case of a high-impedance earthed network, a phase preference logic can be
added to complement the phase selection in case of a cross-country fault. This can
affect the
RELEASE_PE
signals.
In case of a low-impedance earthed network, a faulted loop selection logic can be
added to complement the phase selection in case of a two-phase-to-earth fault.
This can affect the
RELEASE_PE
and
RELEASE_PP
signals.
Faulted phase selection, the voltage-dependent overcurrent method
The "Voltdep overcur" method combines the overcurrent and undervoltage
conditions. The phase current amplitude is compared to the
Str A Ph Sel GFC
threshold setting but a lower current
Lo A Ph Sel GFC threshold is valid during
an undervoltage condition. This increases the sensitivity of the fault detection. The
amplitude of phase-to-earth and phase-to-phase voltages is compared to the
Ph V
Ph Sel GFC and PP V Ph Sel GFC settings. In case of a three-phase fault, the phase-
to-phase voltages are monitored and compared to the
PP V Ph Sel GFC setting.
Earth-fault recognition is always required to release a phase-to-earth
impedance-measuring element.
4
This applies to near three-phase faults. If voltages are still relatively high, all PP releases are
given.
5
This applies to near three-phase faults with EF indication. If voltages are still relatively high, all PE
and PP releases (except ABC Fault) are given.
1MRS759142 F
Protection functions
REX640
Technical Manual
951
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......