
Figure 260: Earth-fault situation in a compensated network
The Petersen coil or the earthing resistor may be temporarily out of operation. To
keep the protection scheme selective, it is necessary to update the
Characteristic
angle setting accordingly. This can be done with an auxiliary input in the protection
relay which receives a signal from an auxiliary switch of the disconnector of the
Petersen coil in compensated networks. As a result the characteristic angle is set
automatically to suit the earthing method used. The RCA_CTL input can be used to
change the operation criteria as described in
Table 532: Relay characteristic angle control in Iosin(φ) and Iocos(φ) operation
criteria
Operation mode
setting:
RCA_CTL
= FALSE
RCA_CTL
= TRUE
Iosin
Actual operation mode: Iosin Actual operation mode: Iocos
Iocos
Actual operation mode: Iocos Actual operation mode: Iosin
Table 533:
Characteristic angle control in phase angle operation mode
Characteristic angle
setting
RCA_CTL
= FALSE
RCA_CTL
= TRUE
-90°
φ
RCA
= -90°
φ
RCA
= 0°
0°
φ
RCA
= 0°
φ
RCA
= -90°
Use of the extended phase angle characteristic
The traditional method of adapting the directional earth-fault protection function
to the prevailing neutral earthing conditions is done with the
Characteristic angle
setting. In an unearthed network,
Characteristic angle is set to -90 degrees and in a
compensated network
Characteristic angle is set to 0 degrees. In case the earthing
method of the network is temporarily changed from compensated to unearthed
due to the disconnection of the arc suppression coil, the
Characteristic angle
setting should be modified correspondingly. This can be done using the setting
Protection functions
1MRS759142 F
462
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......