between the time when the
POSOPEN
auxiliary contact opens and the main contact
is completely open. To incorporate the time t
1
+ t
2
, a correction factor needs to
be added with t
open
to get the actual opening time. This factor is added with the
Opening time Cor (= t
1
+ t
2
) setting. The closing time is calculated by adding the
value set with the
Closing time Cor (t
3
+ t
4
) setting to the measured closing time.
When the setting
Travel time Clc mode is “From Cmd to Pos”, the contact travel
time of the breaker is calculated from the time between the circuit breaker opening
or closing command and the auxiliary contacts’ state change. The opening travel
time is measured between the rising edge of the OPEN_CB_EXE command and the
POSOPEN
auxiliary contact. The closing travel time is measured between the rising
edge of the CLOSE_CB_EXEC command and the POSCLOSE auxiliary contact.
Figure 776: Travel time calculation when Travel time Clc mode is “From Cmd to Pos”
There is a time difference t
1
between the start of the main contact opening and
the OPEN_CB_EXE command. Similarly, there is a time gap t
2
between the time
when the
POSOPEN
auxiliary contact opens and the main contact is completely open.
Therefore, to incorporate the times t
1
and t
2
, a correction factor needs to be added
with t
open
to get the actual opening time. This factor is added with the
Opening
time Cor (= t
2
- t
1
) setting. The closing time is calculated by adding the value set
with the
Closing time Cor(t
4
- t
3
) setting to the measured closing time.
The last measured opening travel time
T_TRV_OP
and the closing travel time
T_TRV_CL
are available in the monitored data view on the LHMI or through tools
via communications.
Alarm limit check
When the measured opening travel time is longer than the value set with the
Open
alarm time setting, the
TRV_T_OP_ALM
output is activated. Respectively, when the
measured closing travel time is longer than the value set with the
Close alarm time
setting, the
TRV_T_CL_ALM
output is activated.
It is also possible to block the
TRV_T_CL_ALM
and
TRV_T_OP_ALM
alarm signals by
activating the
BLOCK
input.
Condition monitoring functions
1MRS759142 F
1364
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......