or mechanical constraint, this starting method is not suitable. The full-voltage
starting produces the highest starting torque. A high starting torque is generally
required to start a high-inertia load to limit the acceleration time. In this method,
full voltage is applied to the motor when the switch is in the "On" position. This
method of starting results in a great initial current surge, which is typically four to
eight times that of the full-load current drawn by the motor. If a star-delta starter is
used, the value of the line current will only be about one-third of the direct-on-line
starting current.
Figure 618: Typical motor starting and capability curves
The start-up supervision of a motor is an important function because of the higher
thermal stress developed during starting. During the start-up, the current surge
imposes a thermal strain on the rotor. This is exaggerated as the air flow for cooling
is less because the fans do not rotate in their full speed. Moreover, the difference of
speed between the rotating magnetic field and the rotor during the start-up time
induces a high magnitude of slip current in the rotor at frequencies higher than
when the motor is at full speed. The skin effect is stronger at higher frequencies
and all these factors increase the losses and the generated heat. This is worse when
the rotor is locked.
The starting current for slip-ring motors is less than the full load current and
therefore it is advisable to use the circuit breaker in the closed position to indicate
the starting for such type of motors.
The starting times vary depending on motor design and load torque characteristics.
The time taken may vary from less than two seconds to more than 60 seconds. The
starting time is determined for each application.
When the permissible stall time is less than the starting time of the motor, the
stalling protection is used and the value of the time delay setting should be set
slightly less than the permissible stall time. The speed switch on the motor shaft
must be used for detecting whether the motor begins to accelerate or not. However,
if the safe stall time is longer than the start-up time of the motor, the speed switch
is not required.
Protection functions
1MRS759142 F
1100
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......