Table 1504:
Live dead mode of operation under which switching can be carried out
Live dead mode
Description
Both Dead
Both line and bus de-energized
Live L, Dead B
Bus de-energized and line energized
Dead L, Live B
Line de-energized and bus energized
Dead Bus, L Any
Both line and bus de-energized or bus de-energized and line
energized
Dead L, Bus Any
Both line and bus de-energized or line de-energized and bus
energized
One Live, Dead
Bus de-energized and line energized or line de-energized and
bus energized
Not Both Live
Both line and bus de-energized or bus de-energized and line
energized or line de-energized and bus energized
When the energizing direction corresponds to the settings, the situation has to be
constant for a time set with the
Energizing time setting before the circuit breaker
closing is permitted. The purpose of this time delay is to ensure that the dead
side remains de-energized and also that the situation is not caused by a temporary
interference. If the conditions do not persist for a specified operation time, the
timer is reset and the procedure is restarted when the conditions allow. The circuit
breaker closing is not permitted if the measured voltage on the live side is greater
than the set value of
Max energizing V.
The measured energized state is available as a monitored data value ENERG_STATE
and as four function outputs
LLDB
(live line / dead bus),
LLLB
(live line / live bus),
DLLB
(dead line / live bus) and
DLDB
(dead line / dead bus), of which only one can
be active at a time. It is also possible that the measured energized state indicates
“Unknown” if at least one of the measured voltages is between the limits set with
the dead and live setting parameters.
Synchro check
The Synchro check function measures the difference between the line voltage and
bus voltage. The function permits the closing of the circuit breaker when certain
conditions are simultaneously fulfilled.
• The measured line and bus voltages are higher than the set values of
Live bus
value and Live line value (ENERG_STATE equals to "Both Live").
• The measured bus and line frequency are both within the range of 95 to 105
percent of the value of f
n
.
• The measured voltages for the line and bus are less than the set value of
Max
energizing V.
In case
Syncro check mode is set to "Syncronous", the additional conditions must be
fulfilled.
• In the synchronous mode, the closing is attempted so that the phase difference
at closing is close to zero.
• The synchronous mode is only possible when the frequency slip is below 0.1
percent of the value of f
n
.
• The voltage difference must not exceed the 1 percent of the value of U
n
.
In case
Syncro check mode is set to “Asyncronous”, the additional conditions must
be fulfilled.
Control functions
1MRS759142 F
1546
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......