STR_LS_LOC
STR_LS_REM
OPR_LS_LOC
OPR_LS_REM
OPR_HS_LOC
OPR_HS_REM
OPR_LS_A
OPR_LS_B
OPR_LS_C
Stabilized
low stage
OR
SEND
STR_LS_A
STR_LS_B
STR_LS_C
OR
SEND
OPR_HS_A
OPR_HS_B
OPR_HS_C
OR
SEND
OPR_LS_A
OPR_LS_B
OPR_LS_C
OR
RECEIVE
STR_LS_A
STR_LS_B
STR_LS_C
OR
RECEIVE
OPR_HS_A
OPR_HS_B
OPR_HS_C
OR
RECEIVE
Inst.
high stage
START
OPERATE
OR
OR
Figure 374: Operation logic of the direct intertrip function
The start and operate signals are provided separately for the low and high stages,
and in the local and remote.
Blocking functionality
There are two independent inputs that can be used for blocking the function:
BLOCK
and
BLOCK_LS
. The difference between these inputs is that
BLOCK_LS
(when TRUE)
blocks only the stabilized low stage leaving the instantaneous high stage operative.
BLOCK
(when TRUE) blocks both stages and also the
PRO_ACTIVE
output is updated
according to the
BLOCK
input status, as described in the Fail safe function chapter.
The
BLOCK
and
BLOCK_LS
input statuses affect only the behavior of the local
protection instance. When a line differential protection stage (stabilized low
or instantaneous high) is blocked, also the received remote signals related to
the corresponding stage are ignored (received direct inter-trip signals from the
remote end). The binary signal transfer functionality should therefore be used for
1MRS759142 F
Protection functions
REX640
Technical Manual
663
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......