Band
width
voltage
U
ΔU
step
t
bandwidth limit
hysteresis limit
U
m
, measured voltage
U
p
, control voltage
T1
s
ta
rt
T1
re
se
t
T1
s
ta
rt
Lowe
r
T1
Figure 916: Voltage-regulating function. A control pulse to lower the voltage is
issued after the elapsed T1.
If the measured voltage is outside the hysteresis when the delay counter T1 reaches
its setting value, the raising or lowering output relay is activated. This activates
either output pulse
RAISE_OWN
or
LOWER_OWN
, and the motor drive of the tap
changer operates. The status of these outputs can be read from the output data
RAISE_OWN
or
LOWER_OWN
.
If the measured voltage falls or rises within the hysteresis limits during the
operating time, the delay counter is reset.
The pulse length can be defined with the
LTC pulse time setting. The default value is
1.5 seconds.
A short delay, same as the typical tap changer operating time, is active before the
start of the next operating timer. For OL5ATCC, the delay is set to 6 seconds. If one
tap changer operation is not enough to regulate the transformer voltage within the
hysteresis limits, a second adjustable delay T2 (
Control delay time 2), usually with
a shorter time setting than T1, starts. This delay is used for the control commands
within the same sequence until the recovery of voltage occurs. The delays T1 and
T2 can be selected either with definite or inverse time characteristics. In the inverse
time mode, the operate time depends on the difference between the control voltage
and the measured voltage as shown in
. The bigger the difference in
the voltage, the shorter the operating time. More information on the inverse time
operation can be found in the
Chapter 9.10.5.8 Timer characteristics
Regulation equation
The simple regulating principle is often complemented by additional features to
take the voltage drop of lines into account (line drop compensation), coordinate the
regulation of parallel transformers and change the voltage level according to the
loading state of the network. The control voltage U
p
is calculated according to the
equation
U
U
U
U
U
p
s
z
ci
rsv
=
+
+
−
(Equation 373)
1MRS759142 F
Control functions
REX640
Technical Manual
1703
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......