Figure 393: Setting range for biased low stage
If the biasing current is small compared to the differential current of the phase
angle between the winding 1 and winding 2 phase currents is close to zero (in
a normal situation, the phase difference is 180 degrees), a fault has most likely
occurred in the area protected by TR2PTDF. Then the internal blocking signals of the
biased stage are inhibited.
Instantaneous high stage
The instantaneous high stage operation can be enabled and disabled with the
Enable high set setting. The corresponding parameter values are "TRUE" and
"FALSE."
The operation of the instantaneous high stage is not biased. The instantaneous
stage operates and the output
OPR_HS
is activated when the amplitude of the
fundamental frequency component of the differential current exceeds the set
High
operate value or when the instantaneous value of the differential current exceeds
2.5 times the value of
High operate value. The factor 2.5 (=1.8 × √2) is due to the
maximum asymmetric short circuit current.
If the biasing current is small compared to the differential current or the phase
angle between the winding 1 and winding 2 phase currents is close to zero (in a
normal situation, the phase difference is 180 degrees), a fault has occurred in the
area protected by TR2PTDF. Then the operation value set for the instantaneous
stage is automatically halved and the internal blocking signals of the biased stage
are inhibited.
Protection functions
1MRS759142 F
692
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......