3.25.1.4
Settings
Table 347: RCHLCCH Settings
Parameter
Values (Range)
Unit
Step
Default
Description
Redundant mode
Off
PRP
HSR
Mode selection for Ethernet
switch on redundant commu-
nication modules. The "None"
mode is used with normal and
Self-healing Ethernet topologies.
Filter Mode A_B
Off
SMV
GOOSE
GOOSE & SMV
Off
Filtering selection for message
types
Goose rate limiter
A_B
0.512...90.000
10.000
Goose rate limit (Mbps)
SMV rate limit A_B
0.512...90.000
70.000
Sampled measured values rate
limit (Mbps)
Def. rate limit A_B
0.512...90.000
8.000
Default rate limit (Mbps)
3.25.1.5
Monitored data
Monitored data is available in four locations.
• Monitoring > Communication > Ethernet > Activity > CHLIV_A
• Monitoring > Communication/ > Ethernet > Activity > REDCHLIV_B
• Monitoring > Communication > Ethernet > Link statuses > LNKLIV_A
• Monitoring > Communication > Ethernet > Link statuses > REDLNKLIV_B
3.25.1.6
Diagnostics
Diagnostics data is available in Monitoring > Communication > Ethernet >
Diagnostics > A_B.
Table 348: Diagnostic parameters for the redundant Ethernet channels LAN A and LAN B
Parameter
Values (Range)
Unit
Step
Default
Description
Reset counters
FALSE / TRUE
FALSE
Reset counters command
GOOSE limit count
0...1000000
0
Goose rate limit exceed count
SMV limit count
0...1000000
0
Sampled measured values limit
exceed count
Ucast limit count
0...1000000
0
Unicast rate limit exceed count
Def. limit count
0...1000000
0
Default rate limit exceed count
GOOSE limit alarm
FALSE / TRUE
FALSE
Goose rate limit exceed alarm
SMV limit alarm
FALSE / TRUE
FALSE
Sampled measured values limit
alarm
Ucast limit alarm
FALSE / TRUE
FALSE
Unicast rate limit exceed alarm
Def. limit alarm
FALSE / TRUE
FALSE
Default rate limit exceed alarm
3.25.2
Ethernet channel supervision SCHLCCH
1MRS759142 F
Basic functions
REX640
Technical Manual
317
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......