
5.3.5
Application
All trip signals from different protection functions are routed through the trip logic.
The most simplified application of the logic function is linking the trip signal and
ensuring that the signal is long enough.
The tripping logic in the protection relay is intended to be used in the three-phase
tripping for all fault types (3ph operating). To prevent the closing of a circuit breaker
after a trip, TRPPTRC can block the CBXCBR closing.
TRPPTRC is intended to be connected to one trip coil of the corresponding circuit
breaker. If tripping is needed for another trip coil or another circuit breaker which
needs, for example, different trip pulse time, another trip logic function can be
used. The two instances of the PTRC function are identical, only the names of the
functions, TRPPTRC1 and TRPPTRC2, are different. Therefore, even if all references
are made only to TRPPTRC1, they also apply to TRPPTRC2.
The inputs from the protection functions are connected to the
OPERATE
input.
Usually, a logic block OR is required to combine the different function outputs to
this input. The
TRIP
output is connected to the binary outputs on the IO board. This
signal can also be used for other purposes within the protection relay, for example
when starting the breaker failure protection.
TRPPTRC is used for simple three-phase tripping applications.
BI#4
Lock-out
reset
OR
PO#1
BI#2
TRPPTRC
OPERATE
RST_LKOUT
TRIP
CCRBRF-trret
T1PTTR-operate
CBXCBR-open
PHLPTOC-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC-operate
NSPTOC1-operate
NSPTOC2-operate
EFLPTOC1-operate
EFHPTOC-operate
EFIPTOC-operate
PDNSPTOC-operate
EFLPTOC2-operate
ARCPSARC1-operate
ARCPSARC2-operate
ARCPSARC3-operate
DARREC-open cb
BLOCK
CL_LKOUT
Figure 668: Typical TRPPTRC connection
1MRS759142 F
Protection related functions
REX640
Technical Manual
1177
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......