50 Hz
Start value Freq
set at 0.975 xFn
Start value df/dt
set at -0.020 xFn/s
Operate Tm df/dt
= 500ms
Operate Tm Freq
= 1000ms
Load shed mode
= Freq< AND df/dt
49 Hz
ST_FRG
OPR_FRG
500ms
1s
OPERATE is not
activated in this case
as Freq< condition not
satisfied
OPERATE
Start of operation timer
Time [s]
Frequency
[Hz]
Figure 518: Load-shedding operation in the “Freq< AND df/dt>” mode when only the
df/dt condition is satisfied ( Rated frequency=50 Hz)
Restore detection
If after the activation of the
OPERATE
output the frequency recovers to a level above
the
Restore start Val setting, the
RESTORE
signal output is activated. The
RESTORE
output remains active for 100 ms. The
Restore mode setting is used to select the
restoring mode to be "Disabled", "Auto" or "Manual".
Restoring mode
Description
Disabled
Load restoration is disabled.
Auto
In the “Auto” mode, input frequency is continuously compared to the
Restore start Val
setting. The restore detection module includes a
timer with the DT characteristics. Upon detection of restoring, the
operation timer activates the
ST_REST
output. When the timer has
reached the value of the
Restore delay time
setting, the
RESTORE
output is activated if the restoring condition still persists. If the fre-
quency drops below the
Restore start Val
before the
RESTORE
output
is activated, the reset timer is activated. If the reset timer reaches
the value of the
Reset delay time
setting, the timer resets and the
ST_REST
start output is deactivated.
Manual
In the “Manual” mode, a manual restoration is possible through the
MAN_RESTORE
input or via communication. The
ST_REST
output is
activated if the
MAN_RESTORE
command is available and the frequen-
1MRS759142 F
Protection functions
REX640
Technical Manual
933
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......