
needs to be compensated to provide a correct differential current calculation result
on both ends.
The operation characteristics related settings are given in units as percentage of
the current transformer secondary nominal current on each line end protection
relay. For the actual primary setting, the corresponding CT ratio on each line end
has to be considered. An example of how the
CT ratio correction parameter values
should be selected on both line ends in the example case to compensate the
difference in the nominal levels can be presented.
Another example for differential application without in-zone transformer where line
rated current is 400 A. The ratio of CTs are 800/1 and 400/1.
Figure 366: Example of CT ratio correction setting calculation in line differential
application
The settings for
CT ratio Corrections for protection relay A and protection relay (B)
are:
CT ratio Correction (A) = 800 A / 400 A = 2.000
CT ratio Correction (B) = 400 A / 400 A = 1.000
The CT secondary current often differs from the rated current at the rated load of
the power transformer. The CT transforming ratio can be corrected on both sides of
the power transformer with the
CT ratio Correction setting.
First, the rated load of the power transformer is calculated on both sides when the
apparent power and phase-to-phase voltage are known.
I
S
U
nT
n
n
=
×
3
(Equation 144)
I
nT
Rated load of the power transformer
S
n
Rated power of the power transformer
U
n
Rated phase-to-phase voltage
Next, the settings for the CT ratio correction can be calculated with the formula:
1MRS759142 F
Protection functions
REX640
Technical Manual
649
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......