occurs after the
Event delay setting. A common three-position status is indicated at
variable POSITION.
Table 1485: Status indication for a three-position switch based on auxiliary contacts
Status
Inputs
Outputs
POSITIO
N
DCPOSCL
OSE
DCPOSO
PEN
ESPOSCL
OSE
ESPOSOP
EN
REED
DCCLOSE
_POS
DCOPEN_
POS
ESCLOSE
_POS
ESOPEN_
POS
OKPOS
Discon-
nector
closed
1
0
0
1
x
1
0
0
1
1
Discon-
nector in-
termedi-
ate
0
0
0
1
x
0
0
0
1
0
Both
open
0
1
0
1
x
0
1
0
1
1
Earthing
switch in-
termedi-
ate
0
1
0
0
x
0
1
0
0
0
Earthing
switch
closed
0
1
1
0
1
1
0
1
1
0
1
Faulty
0
1
1
0
0
2
0
1
0
0
0
Faulty
0
1
1
1
x
0
1
0
0
0
Faulty
1
1
0
1
x
0
0
0
1
0
Faulty
1
x
1
x
x
0
0
0
0
0
Faulty
x
0
x
0
x
0
0
0
0
0
x = no difference
The
REED
input is only supervised during a short time window when earthing switch
has closed and if
Reed contact setting is set as "Available".
9.3.5
Application
In the field of distribution and sub-transmission automatic, reliable control and
status indication of primary switching components both locally and remotely is of
significant importance. They are needed especially in modern remotely controlled
substations.
P3SSXSWI is designed to be used for status indication of a three-state (earthing
switch closed, disconnector closed and both open) switch.
9.3.6
Signals
1
REED
input has been detected as closed within time-out and earthing switch is indicated as
closed.
2
REED
input has not been detected as closed within time-out and faulty position is indicated.
1MRS759142 F
Control functions
REX640
Technical Manual
1537
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......