DC restraint
On detection of a DC component, the function temporarily desensitizes the
differential protection. The functioning of this module depends on the
DC restrain
Enable setting. The DC components are continuously extracted from the three
instantaneous differential currents. The highest DC component of all three is taken
as a kind of DC restraint in a sense that the highest effective, temporary sensitivity
of the protection is temporarily decreased as a function of this highest DC offset.
The calculated DC restraint current is not allowed to decay (from its highest ever
measured value) faster than with a time constant of one second. The value of the
temporarily effective sensitivity limit is limited upwards to the rated current of the
machine or 3.3 times that of
Low operate value, whichever is smaller. The temporary
extra limit decays exponentially from its maximum value with a time constant of one
second.
This feature should be used in case of networks where very long time constants
are expected. The temporary sensitivity limit is higher to the set operating
characteristics. In other words, the temporary limit has superposed the unchanged
operating characteristics and temporarily determines the highest sensitivity of the
protection. The temporary sensitivity is less than the sensitivity in section 1 of the
operating characteristic and is supposed to prevent an unwanted trip during the
external faults with lower currents.
Biased low stage
The current differential protection needs to be biased because of the possible
appearance of a differential current which can be due to something else than an
actual fault in the machine. In case of differential protection, a false differential
current can be caused by:
• CT errors
• CT saturation at high currents passing through the machine
The differential current caused by CT errors increases at the same percent ratio as
the load current.
The high currents passing through the protected object can be caused by the
through fault. Therefore, the operation of the differential protection is biased with
respect to the load current. In the biased differential protection, the higher the
differential current required for the protection of operation, the higher the load
current.
Based on the conditions checked from the through-fault module, the DC
(component) detection module and the CT saturation-based blocking modules,
the biased low-stage module decides whether the differential current is due to
the internal faults or some false reason. In case of detection of the TF, DC or CT
saturation, the internal differential blocking signal is generated, which in turn blocks
the operating signal. In case of internal faults, the operation of the differential
protection is affected by the bias current.
The
Low operate value setting for the stabilized stage of the function block is
determined with the equation:
Low operate value
I
d
=
1
(Equation 203)
The
Slope section 2 and Slope section 3 settings are determined correspondingly:
1MRS759142 F
Protection functions
REX640
Technical Manual
791
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......