
F
n
the rated accuracy limit factor corresponding to the rated burden S
n
I
2n
the rated secondary current of the CT
R
in
the secondary internal resistance of the CT
S
n
the volt-amp rating of the CT
The formulas are based on choosing the CTs according to
,
which results an absolutely stable scheme. In some cases, it is possible
to achieve stability with knee point voltages lower than stated in the
formulas. The conditions in the network, however, have to be known well
enough to ensure the stability.
1. If U
k
≥ 2 x U
s
, fast protection relay operation is secure.
2. If U
k
≥ 1.5 x U
s
and < 2 x U
s
, protection relay operation can be
slightly prolonged and should be studied case by case.
If U
k
< 1.5 x U
s
, the protection relay operation is jeopardized.
Another CT has to be chosen.
The need for the VDR depends on certain conditions.
First, voltage U
max
, ignoring the CT saturation during the fault, is calculated with
the equation
U
I
n
R
R
R
I
n
R
k
in
in
m
s
k
in
s
max
max
max
=
×
+
+
(
)
≈
×
(Equation 187)
I
kmaxin
the maximum fault current inside the zone, in primary amps
n
the turns ration of the CT
R
in
the internal resistance of the CT in ohms
R
m
the resistance of the longest loop of the CT secondary circuit, in ohms
R
s
the resistance of the stabilized resistor, in ohms
Next, the peak voltage û, which includes the CT saturation, is estimated with the
formula (given by P.Mathews, 1955)
û
U
U
U
kn
kn
=
−
(
)
2 2
max
(Equation 188)
U
kn
the knee point voltage of the CT
The VDR is recommended when the peak voltage û ≥ 2kV, which is the insulation
level for which the protection relay is tested.
If R
s
was smaller, the VDR could be avoided. However, the value of R
s
depends on
the protection relay operation current and stabilizing voltage. Thus, either a higher
setting must be used in the protection relay or the stabilizing voltage must be
lowered.
1MRS759142 F
Protection functions
REX640
Technical Manual
767
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......