Type of fault
Fault detection criteria
Output
activation
(Check if the local reactive power (Q) is deviating
significantly from other generators in the same net-
work)
Under excitation
fault
Number of generators in parallel with same gover-
nor mode >= 3
AND
MAX(Q1, Q2, … Q8) – MIN(Q1, Q2 … Q8) <
Max Q Dev
Vot
AND
Q < MIN(Q1, Q2 … Q8) -
Max Q Dev Vot
UN_EXCT_FLT
Among the 8 reactive power inputs,
Q1 … Q8
, the input corresponding
to the setting
Local generator Num, would be considered as the local
reactive power. For example, if
Local generator Num is set to "1", then
Q1
is considered as the local generator reactive power output.
Fuel rack position monitoring
This module compares the position of the engine’s fuel rack, obtained as input
FUEL_RCK_POS
, to the active power, P. The
FUEL_RCK_POS
input is a 0-20mA signal
obtained through an
RTD
input. An offset linear relationship, refer
, is
assumed between the fuel rack position and the generator active power.
The droop characteristics can be parameterized using the settings
Rack Pos no load
and
Rack Pos gain. If the performance of the generator set deviates over/under
the set droop curve, the fuel rack system is identified as faulty and the output
FUEL_RCK_FLT
is activated. The module can be disabled using the setting
Disable
Fuel Rck Mon.
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1415
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......