9.2
Three-state disconnector control P3SXSWI (ANSI
29DS/GS)
9.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-state disconnector control
P3SXSWI
I<->O P3S
29DS/GS
9.2.2
Function block
Figure 831: Function block
9.2.3
Functionality
The three-state disconnector control function P3SXSWI is used to control a three-
state switch (disconnector closed, both open, earthing switch closed) and to
provide status information on the MV air-insulated switchgear (AIS) and gas-
insulated switchgear (GIS). P3SXSWI executes commands to RIO600 SCM or directly
drives the switchgear motor by direct control of the protection relay’s H-bridge
(if available). The function evaluates blocking conditions and different supervision
conditions and it performs an execution command only if all conditions are fulfilled.
If erroneous conditions occur, the function indicates an appropriate cause value.
The function is designed according to the IEC 61850-7-4 standard including logical
nodes CILO, CSWI and XSWI.
P3SXSWI has operation counters for disconnector operation and earthing switch
operation. The counter values can be read and written remotely from the place of
operation or via LHMI.
Control functions
1MRS759142 F
1520
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......